Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
93
Table 39. System parameters.
Code
Parameter
Min
Max
Default
ID
Note
P2.6
Parity type
0
2
0
813
0
= None
1
= Even
2
= Odd
The Stop Bit is 2-bit when Parity type is
0
= None;
The Stop Bit is 1-bit when Parity type is
1
= Even or
2
= Odd
P2.7
Communication time out
0
255
10
814
0
= Not used
1
= 1 sec
2
= 2 secs, etc
P2.8
Reset communication status
0
1
0
815
When OPTBH board has been installed, the comm.-parameters are as follows
P2.1
Sensor 1 type
0
6
0
14072
0
= No Sensor
1
= PT100
2
= PT1000
3
= Ni1000
4
= KTY84
5
= 2 × PT100
6
= 3 × PT100
P2.2
Sensor 2 type
0
6
0
14073
0
= No Sensor
1
= PT100
2
= PT1000
3
= Ni1000
4
= KTY84
5
= 2 × PT100
6
= 3 × PT100