9.1.14 PID control parameters (Control panel: Menu PAR
P14)
Table 35. PID control parameters.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P14.1
Setpoint source selection
0
Varies
0
332
0
= Fixed setpoint %
1
= AI1
2
= AI2
3
= ProcessDataIn1 (0 -100%)
4
= ProcessDataIn2 (0 -100%)
5
= ProcessDataIn3 (0 -100%)
6
= ProcessDataIn4 (0 -100%)
7
= AIE1
8
= Temperature input 1
9
= Temperature input 2
10
= Temperature input 3
P14.2
Fixed setpoint 1
0,0
100,0
50,0
167
Fixed setpoint
P14.3
Fixed setpoint 2
0,0
100,0
50,0
168
Alternative fixed setpoint, selectable with DI
P14.4
Feedback source selection
0
Varies
1
334
0
= AI1
1
= AI2
2
= ProcessDataIn1 (0 -100%)
3
= ProcessDataIn2 (0 -100%)
4
= ProcessDataIn3 (0 -100%)
5
= ProcessDataIn4 (0 -100%)
6
= AI2-AI1
7
= AIE1
8
= Temperature input 1
9
= Temperature input 2
10
= Temperature input 3
P14.5
Feedback value minumum
0,0
50,0
%
0,0
336
Value at minimum signal
P14.6
Feedback value maximum
10,0
300,0
%
100,0
337
Value at maximum signal
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...