Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
103
Table 41.
Explanations
1
Control signal (CS) 1 actives causing the output frequency to rise.
The motor runs forward.
8
Run enable signal is not active what prevents the drive from starting
(not ready) a digital input has been configured on par. 5.7
2
If start forward signal [CS1] and start reverse signal [CS2] are active
simultaneously, there is alarm 55 Conflict FWD/REW.
9
Run enable signal is active, which causes the frequency to rise
towards the set frequency because CS1 is still active.
3
CS1 is inactivated which caused the direction to start changing
(FWD to REV) because CS2 is still active, and alarm 55 disappears.
10
Keypad stop button is pressed and the frequency output drops to
0 Hz. (This signal only works if Par. 2.7 [Keypad stop button] = 1)
4
CS2 is inactivated and the frequency drops to 0 Hz.
11
The drive starts through pushing the Start button on the keypad.
5
CS2 actives again causing the motor to accelerate (REV) towards the
set frequency.
12
The keypad stop button is pushed again to stop the drive.
(This signal only works if Par. 2.7 [Keypad stop button] = 1)
6
CS2 inactivates and the frequency output drops to 0 Hz.
13
The attempt to start the drive through pushing the Start button is not
successful because CS1 is inactive.
7
CS1 actives and the motor accelerates (FWD) towards the set
frequency.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...