Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
61
9.1.1 Motor settings (Control panel: Menu PAR -> P1)
Table 22. Motor settings
Code Parameter
Min
Max
Unit
Default
ID
Note
P1.1 Motor nominal voltage
180
480
V
Varies
110
P1.2 Motor nominal frequency
30,00
320,00
Hz
50,00/60,00
111
P1.3 Motor nominal speed
30
20000
rpm
1440/1720
112
P1.4 Motor nominal current
0,2 × I
Nunit
2,0 × I
Nunit
A
I
Nunit
113
P1.5 Motor cos
φ
(Power Factor)
0,30
1,00
0,85
120
P1.6 Motor type
0
1
0
650
0
= Induction
1
= Permanent magnet
P1.7 Current limit
0,2 × I
Nunit
2,0 × I
Nunit
A
1,5 × I
Nunit
107
P1.8 Motor control mode
0
1
0
600
0
= Frequency control
1
= Open loop speed control
P1.9 U / f ratio
0
2
0
108
0
= Linear
1
= Square
2
= Programmable
P1.10 Field weakening point
8,00
320,00
Hz
50,00/60,00
602
P1.11 Field weakening point
voltage
10,00
200,00
%
100,00
603
P1.12 U / f mid point frequency
0,00
P1.10
Hz
50,00/60,00
604
P1.13 U / f mid point voltage
0,00
P1.11
%
100,00
605
P1.14 Zero freq voltage
0,00
40,00
%
Varies
606
P1.15 Torque Boost
0
1
0
109
0
= Disabled
1
= Enabled
P1.16 Switching frequency
1,5
16,0
kHz
4,0/2,0
601
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...