Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
119
10.7 Digital outputs
(Control panel: Menu PAR
P7)
RO1 signal selection
RO2 signal selection
DO1 signal selection
Table 51.Outputsignals via RO1, RO2 and DO1
Setting
Signal content
0
= Not used
Output is not in operation.
1
= Ready
The frequency converter is ready to operate.
2
= Run
The frequency converter operates
(motor is running).
3
= Fault
A fault trip has occurred.
4
= Fault inverted
A fault trip has not occurred.
5
= Warning
A warning is active.
6
= Reversed
The reverse command has been selected, out-
put frequency to the motor is negative.
7
= At speed
The output frequency has reached the set
reference.
8
= Motor regulator
active
All motor monitoring functions are activated
(e.g., over current regulator, over voltage regu-
lator, under voltage regulator, etc.)
9
= FB Control
Word.B13
Output can be controlled with B13 in the
fieldbus control word.
10
= FB Control
Word.B14
Output can be controlled with B14 in the
fieldbus control word.
11
= FB Control
Word.B15
Output can be controlled with B15 in the
fieldbus control word.
Setting
Signal content
12
= Output
frequency superv.
Output frequency is over / under the limits,
set with parameters P11.1 and P11.2.
13
= Output
torque superv.
Motor torque is over/under the limit, set with
parameter P11.3 and P11.4
14
= Unit
temperature superv.
Unit temperature is over / under the limits,
set with parameters P11.5 and P11.6.
15
= Analogue
input superv.
Analogue inputs set with parameter P11.7 is
over / under the limits, set in P11.8 and P11.9.
16
= Preset Speed
Active
Each of preset speeds are activated.
17
= External
Brake control
External Brake control.
Closed = Brake open,
Open = Brake closed.
18
= Keypad
control active
Keypad is set as the current control place.
19
= I/O control
active
I/O is set as the current control place.
20
= Fire mode
active
21
= Temperature
supervision
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...