Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
36
Fault code Fault name
Possible cause
Correcting actions
9
Under voltage
The DC-link voltage has gone below the internal
safety limit:
• most probable cause: supply voltage is too low
• frequency converter internal fault
• power outages
In case of temporary supply voltage break reset the
fault and restart the frequency converter.
Check the supply voltage. If it is adequate, an internal
failure has occurred.
Contact the distributor near to you.
10
Input phase fault
Input phase is missing
Check supply voltage, fuses and cable.
11
Output phase fault
Current measurement has detected that there is no
current in one motor phase.
Check motor cable and motor.
13
Frequency converter
under temperature
Heat sink temperature is under 14 °F (–10 °C)
Check the ambient temperature.
14
Frequency converter over
temperature
Heat sink is overheated.
Check that the cooling air flow is not blocked.
Check the ambient temperature.
Clean the heatsink dust.
Make sure that the switching frequency is not too high
in relation to ambient temperature and motor load.
15
Motor stalled
Motor stall protection has tripped.
Check that the motor is able to rotate freely.
16
Motor over temperature
Motor overheating has been detected by frequency
converter motor temperature model.
Motor is overloaded.
Decrease the motor load.
If no motor overload exists, check the temperature
model parameters.
17
Motor underload
Motor underload protection has tripped.
Check motor and load, , as well as the low load
detection parameters (P11.14 - P11.16).
E.g. for broken belts or dry pumps.
22
EEPROM checksum fault Parameter save fault
• faulty operation
• component failure
Contact the distributor near to you.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...