Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
63
Table 22. Motor settings
Code Parameter
Min
Max
Unit
Default
ID
Note
P1.24 I/f start enable
0
1
0
534
The I/f Start function is typically used with perma-
nent magnet motors (PM) to start the motor with
constant current control. This is useful with high
power motors in which the resistance is low and
the tuning of the U/f curve difficult.
Applying the I/f Start function may also prove
useful in providing sufficient torque for the motor
at startup.
0
= Disabled
1
= Enable
P1.25 I/f start frequency
reference limit
1
100
%
10
535
Output frequency limit below which the defined I/f
start current is fed to motor.
P1.26 I/f start current reference
0
100.0
%
80.0
536
The current fed to the motor when the I/f start
function is activated.
P1.27 Voltage limiter enable
0
1
1
1079
Voltage limiter function addresses problem with
very high DC-link voltage ripple with 1-phase
drives when fully loaded. Very high ripple in DC link
voltage will transform to high current and torque
ripple, which can disturb some users.
Voltage limiter function limits maximum output
voltage to bottom of DC-voltage ripple. This reduc-
es current and torque ripple, but decreases max-
imum output power since voltage is limited and
more current is needed.
0
= Disabled
1
= Enable
NOTE:
These parameters are shown, when P16.2 = 0.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...