Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
138
11 Technical data
11.1 HVAC232/402 technical data
Table 58. HVAC232/402 technical data.
Mains
connection
Input voltage U
in
208 … 240 V, -15% … +10% 1~
380 … 480 V, -15% … +10% 3~
Input frequency
45 … 66 Hz
Connection to mains
Once per minute or less (normal case)
Supply
network
Networks
HVAC232/402 cannot be used with corner grounded networks
Short circuit current
Maximum short circuit current has to be < 50 kA
Motor
connection
Output voltage
0 - U
in
Output current
Continuous rated current I
N
at ambient temperature max. +50 ºC (depends on the unit size),
overload 1.5 × I
N
max 1 min / 10 min
Starting current / torque
Current 2 × I
N
for 2 sec in every 20 sec period. Torque depends on motor
Output frequency
0 … 320 Hz
Frequency resolution
0,01 Hz
Control
connection
Digital input
Positive, Logic "1": 18 … +30 V, Logic "0": 0 … 5 V;
Negative, Logic "1": 0 … 10 V, Logic "0": 18 … 30 V; Ri = 10 K
Ω
(floating)
Analogue input
voltage
0 … +10 V,Ri = 250 K
Ω
Analogue input
current
0(4) … 20 mA, Ri ≤ 250
Ω
Analogue output
0 … 10 V, RL ≥ 1K
Ω
; 0(4) … 20 mA, RL ≤ 500
Ω
, Selectable through microswitch
Digital output
Open collector, max. load 35V/50mA (floating)
Relay output
Switching load: 250 Vac/3 A, 24 V DC 3 A
Auxiliary voltage
±20%, max. load 50 mA
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...