Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
58
Table 21. Quick setup parameters.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P14.4 Feedback source selection
0
Varies
1
334
0
= AI1
1
= AI2
2
= ProcessDataIn1(0-100%)
3
= ProcessDataIn2(0-100%)
4
= ProcessDataIn3(0-100%)
5
= ProcessDataIn4(0-100%)
6
= AI2-AI1
7
= AIE1
8
= Temperature input 1
9
= Temperature input 2
10
= Temperature input 3
P14.5 Feedback value min
0,0
50,0
%
0,0
336
Value at minimum signal
P14.6 Feedback value max
10,0
300,0
%
100,0
337
Value at maximum signal
P14.11 Sleep min frequency
0,00
P3.2
Hz
25,00
1016
Threshold for enter sleep
P14.12 Sleep delay
0
3600
s
30
1017
Delay for enter sleep
P14.13 Wake up level
0,0
100,0
%
90,0
1018
Threshold for exit sleep
P14.14 Sleep setpoint boost
0,0
50,0
%
10,0
1071
Referred to setpoint
P14.15 Setpoint boost time
0
60
s
10
1072
Boost time after P14.12
P16.2 Parameter conceal
0
1
1
115
Hides all parameters not in quick start
0
= All parameters visible
1
= Only quick setup parameter group
visible
P18.1 Fire mode password
0
9999
0
1599
1234
= Test mode
1001
= Enable
1515
= Disable
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...