Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
57
Table 21. Quick setup parameters.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P3.5
Preset speed 2
P3.1
P3.2
Hz
15,00
106
P3.7
Preset speed 3
P3.1
P3.2
Hz
20,00
126
P4.2
Acceleration time 1
0,1
3000,0
s
3,0
103
P4.3
Declaration time 1
0,1
3000,0
s
3,0
104
P6.1
AI1 range
0
1
0
379
P6.5
AI2 range (see the P6.1)
0
1
0
390
P10.1 Prohibit
frequency range 1 low limit
0,00
P3.2
Hz
0,00
509
P10.2 Prohibit
frequency range 1 high limit
0,00
P3.2
Hz
0,00
510
P13.1 Automatic reset
0
1
0
731
P14.1 Setpoint source selection
0
Varies
0
332
0
= Fixed setpoint %
1
= AI1
2
= AI2
3
= ProcessDataIn1(0-100%)
4
= ProcessDataIn2(0-100%)
5
= ProcessDataIn3(0-100%)
6
= ProcessDataIn4(0-100%)
7
= AIE1
8
= Temperature input 1
9
= Temperature input 2
10
= Temperature input 3
P14.2 Fixed setpoint 1
0,0
100,0
%
50,0
167
Fixed setpoint
P14.3 Fixed setpoint 2
0,0
100,0
%
50,0
168
Alternative fixed setpoint,
selectable with DI
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...