Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
51
Table 20. Monitoring values
Code
Monitoring signal
Unit
ID
Description
V1.1
Output frequency
Hz
1
Output frequency to motor
V1.2
Frequency reference
Hz
25
Frequency reference to motor control
V1.3
Motor speed
rpm
2
Calculated motor speed
V1.4
Motor current
A
3
Measured motor current
V1.5
Motor torque
%
4
Calculated actual / nominal torque of the motor
V1.6
Motor shaft power
%
5
Calculated actual / nominal power of the motor
V1.7
Motor voltage
V
6
Motor voltage
V1.8
DC-link voltage
V
7
Measured DC-link voltage
V1.9
Unit temperature
°C
8
Heatsink temperature
V1.10
Motor temperature
%
9
Calculated motor temperature
V1.11
Output Power
kW
79
Output power from drive to motor
V2.1
Analogue input 1
%
59
AI1 signal range in percent of used range
V2.2
Analogue input 2
%
60
AI2 signal range in percent of used range
V2.3
Analogue output
%
81
AO signal range in percent of used range
V2.4
Digital input status DI1, DI2, DI3
15
Digital input status
V2.5
Digital input status DI4, DI5, DI6
16
Digital input status
V2.6
RO1, RO2, DO
17
Relay / digital output status
V2.11
Analogue input E1
%
61
Analogue input signal 1 in % from option board, hidden until an option board is connected
V2.12
Analogue output E1
%
31
Analogue output signal 1 in % from option board, hidden until an option board is connected
V2.13
Analogue output E2
%
32
Analogue output signal 2 in % from option board, hidden until an option board is connected
V2.14
DIE1, DIE2, DIE3
33
This monitor value shows status of the digital inputs 1-3 from option board, hidden until an option board is connected
V2.15
DIE4, DIE5, DIE6
34
This monitor value shows status of the digital inputs 4-6 from option board, hidden until an option board is connected
V2.16
DOE1, DOE2, DOE3
35
This monitor value shows status of the relay outputs 1-3 from option board, hidden until an option board is connected
V2.17
DOE4, DOE5, DOE6
36
This monitor value shows status of the relay outputs 4-6 from option board, hidden until an option board is connected
V2.18
Temperature input 1
50
Measured value of Temperature input 1 in temperature unit (Celsius or Kelvins) by parameter setting,
hidden until an option board is connected
V2.19
Temperature input 2
51
Measured value of Temperature input 2 in temperature unit (Celsius or Kelvins) by parameter setting,
hidden until an option board is connected
V2.20
Temperature input 3
52
Measured value of Temperature input 3 in temperature unit (Celsius or Kelvins) by parameter setting,
hidden until an option board is connected
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...