Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
42
6.2
Control I/O
Table 17. HVAC232/402 General purpose application default I/O configuration and connections for control board
1–10 k
Ω
Terminal
Signal
Factory preset
Description
1
+10 Vref
Ref. voltage out
Maximum load 10 mA
2
AI1
Analogue signal in 1
Freq. reference
P)
0 … 10 V, Ri = 250 k
Ω
3
GND
I/O signal ground
6
24 Vout
24 V output for DI's
±20%, max. load 50 mA
7
DI_C
Digital Input Common
Digital Input Common for DI1-DI6, refer to „Table 18. DI Sink Type“ on page 40
8
DI1
Digital input 1
Start forward
P)
Positive Logic 1: 18 … 30 V,
Negative Logic 1: 0 … 10 V,
Positive Logic 0: 0 … 5 V,
Negative Logic 0: 18 … 30 V;
Ri = 10 k
Ω
(floating)
9
DI2
Digital input 2
Start reverse
P)
10
DI3
Digital input 3
Fault reset
P)
A
A
RS-485 signal A
FB Communication
Negative
B
B
RS-485 signal B
FB Communication
Positive
4
AI2
Analogue signal in 2
PID actual value and Freq.
reference
P)
Default: 0(4) … 20 mA, Ri ≤ 250
Ω
Other: 0 … +10 V, Ri = 250 k
Ω
Selectable through microswitch
5
GND
I/O signal ground
13
DO-
Digital Output Common
Digital Output Common
14
DI4
Digital input 4
As DI1
15
DI5
Digital input 5
As DI1, Selectable through microswitch
16
DI6
Digital input 6
As DI1
18
AO
Analogue Output
Output frequency
P)
0(4) … 20 mA, RL ≤ 500
Ω
, 0 … 10 V, RL ≥ 1 k
Ω
, Selectable through microswitch
20
DO
Digital signal out
Active = READY P)
Open collector, max. load 35 V / 50 mA
22
RO1 NO
Relay out 1
Active = RUN P)
Switching load: 23 RO1 CM 250 Vac / 3 A, 24 Vdc 3 A
23
RO1 CM
24
RO2 NC
Relay out 2
Active = FAULT P)
Switching load:
25 RO2 CM 250 Vac / 3 A, 24V DC 3A
25
RO2 CM
26
RO2 NO
P) = Programmable function, see parameter lists and descriptions, Chapters „9
Standard application parameters“ on page 55 and „10
Parameter description“ on page 96.
mA
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...