Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
73
9.1.7 Digital outputs (Control panel: Menu PAR
P7)
Table 28. Digital outputs.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P7.1
RO1 signal selection
0
Varies
2
313
0
= Not used
1
= Ready
2
= Run
3
= Fault
4
= Fault Inverted
5
= Warning
6
= Reversed
7
= At Speed
8
= Motor regulator active
9
= FB Control Word.B13
10
= FB Control Word.B14
11
= FB Control Word.B15
12
= Output freq superv.
13
= Output torque superv.
14
= Unit temperature superv.
15
= Analogue input superv.
16
= Preset Speed Active
17 = External Brake ctrl
18 = Keypad control active
19 = I/O control active
20 = fire mode
21 = temperature supervision
P7.2
RO2 signal selection
0
Varies
3
314
As parameter 7.1
P7.3
DO1 signal selection
0
Varies
1
312
As parameter 7.1
P7.4
RO2 inversion
0
1
0
1588
0
= No inversion
1
= Inverted
P7.5
RO2 ON delay
0,00
320,00
s
0,00
460
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...