
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
59
Table 21. Quick setup parameters.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P18.2 Fire mode frequency select
0
Varies
0
1617
Fire mode frequency preset
NOTE!
This parameter will be locked
when fire mode is active. To change
the parameter you have to disable fire
mode.
P18.3 Fire mode frequency preset
P3.1
P3.2
Hz
8,00
1598
Fire mode frequency preset
NOTE!
This parameter will be locked
when fire mode is active. To change
the parameter you have to disable fire
mode.
P18.4 Fire mode activation close
0
Varies
6
1619
Digital input normal close
As parameter 5.1
NOTE!
This parameter will be locked
when fire mode is active. To change
the parameter you have to disable
fire mode.
P18.5 Fire mode activation open
0
Varies
0
1596
Digital input normal open
As parameter 5.1
NOTE!
This parameter will be locked
when fire mode is active. To change
the parameter you have to disable
fire mode.
P18.6 Fire mode reverse
0
Varies
0
1618
Reverse command of rotation direction
while running in fire mode. This DI has
no effect in normal operation.
As parameter 5.1
NOTE!
This parameter will be locked
when fire mode is active. To change
the parameter you have to disable
fire mode.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...