Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
79
9.1.11 Limit Supervisions (Control panel: Menu PAR
P11)
Table 32. Limit Supervisions.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P11.1
Output frequency supervision
function
0
2
0
315
0 = Not used
1
= Low limit
2
= High limit
P11.2
Output frequency supervision
limit
0,00
P3.2
Hz
0,00
316
P11.3
Torque supervision
function
0
2
0
348
0 = Not used
1
= Low limit
2
= High limit
P11.4
Torque supervision
limit
0,0
300,0
%
0,0
349
P11.5
Unit Temperature Supervision
0
2
0
354
P11.6
Unit Temperature Supervision Limit
–10
100
°C
40
355
P11.7
Analogue input supervision
signal
0
Varies
0
356
0 = AI1
1
= AI2
2
= AIE1
P11.8
AI superv ON level
0,00
100,0
%
80,00
357
P11.9
AI superv OFF level
0,00
100,00
%
40,00
358
P11.10 Temperature supervision
input
1
7
1
1431
Binary-coded selection of signals to use
for temperature supervision
B0
= Temperature input 1
B1
= Temperature input 2
B2
= Temperature input 3
NOTE!
Hidden until an option board
is connected.
P11.11 Temperature supervision function
0
2
2
1432
As parameter 11.1, hidden until an option
board is connected.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...