Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
65
9.1.2 Start / stop setup (Control panel: Menu PAR
P2)
Table 23. Start / stop setup.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P2.1
Remote Control Place 1 Selection
0
2
0
172
0
= I/O terminals
1
= Fieldbus
2
= Keypad
P2.2
Start function
0
1
0
505
0
= Ramping
1
= Flying start
P2.3
Stop function
0
1
0
506
0
= Coasting
1
= Ramping
P2.4
I/O Start / Stop logic
0
4
0
300
I/O control
I/O control
signal1
signal2
0
= Forward
0
= Reverse
1
= Fwd(edge)
1
= Inverted Stop
2
= Fwd(edge)
2
= Bwd(edge)
3
= Start
3
= Reverse
4
= Start(edge)
4
= Reverse
P2.5
Local / Remote
0
1
0
211
0
= Remote control
1
= Local control
P2.6
Keypad control direction
0
1
0
123
0
= Forward
1
= Backward
P2.7
Keypad stop button
0
1
1
114
0
= Inactive
1
= Active
P2.8
Remote Control Place 2 Selection
0
2
0
173
0
= I/O terminals
1
= Fieldbus
2
= Keypad
P2.9
keypad button lock
0
1
0
15520
0
= unlock all keypad button
1
= Loc/Rem button locked
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...