Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
30
Table 9. Cable and fuse sizes for HVAC232/402, 208 - 240 V, 1~
Frame
Power
[kW]
Fuse
[A]
Mains cable
Cu [mm
2
]
Motor cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0.25…0.55
10
2
×
1.5+1.5
3
×
1.5+1.5
1.5…4
1.5…4
0.5…1.5
0.5…1.5
MI2
0.75…1.50
20
2
×
2.5+2.5
3
×
1.5+1.5
1.5…4
1.5…4
0.5…1.5
0.5…1.5
MI3
2.2*
32
2
×
6+6
3
×
1.5+1.5
1.5…6
1.5…6
0.5…1.5
0.5…1.5
*
The maximum ambient operating temperature of this drive is 40 °C!
Table 10. Cable and fuse sizes for HVAC232/402, 380 - 480 V, 3~
Frame
Power
[kW]
Fuse
[A]
Mains cable
Cu [mm
2
]
Motor cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0.37…0.75
6
3
×
1.5+1.5
3
×
1.5+1.5
1.5…4
1.5…4
0.5…1.5
0.5…1.5
MI2
1.1…2.2
10
3
×
1.5+1.5
3
×
1.5+1.5
1.5…4
1.5…4
0.5…1.5
0.5…1.5
MI3
3.0…5.5
20
3
×
2.5+2.5
3
×
2.5+2.5
1.5…6
1.5…6
0.5…1.5
0.5…1.5
MI4
7.5…25.5
20
3
×
6+6
3
×
6+6
1…10Cu
1…10
0.5…1.5
0.5…1.5
MI5
15…18.5
40
3
×
10+10
3
×
10+10
2.5…50 Cu/Al
2.5…35
0.5…1.5
0.5…1.5
NOTE:
To fulfil standard EN61800-5-1, the protective conductor should be
at least 10 mm
2
Cu or 16 mm
2
Al
. Another possibility is to use an additional
protective conductor of at least the same size as the original one.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...