Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
142
12.2 Low overload
Low overload = 150% starting torque, 2 sec/20 sec, 110% overloadability,
1 min/10 min
Following continuous operation at rated output current,110% rated output
current (IL) for 1 min, followed by a period of load current less than rated
current, and of such duration that the r.m.s output current, over the duty
cycle, does not exceed rated output current (IL).
12.3 High overload
High overload = 200% starting torque, 2 sec/20 sec, 150% overloadability,
1 min/10 min
Following continuous operation at rated output current, 150 % rated out-
put current (IH) for 1 min, followed by a period of load current less than rat-
ed current, and of such duration that the r.m.s output current, over the duty
cycle, does not exceed rated output current (IH).