Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
128
10.13 PID control parameters
(Control panel: Menu PAR
P14)
Feedback value minimum
Feedback value maximum
This parameter sets the minimum and maximum scaling points for feed-
back value.
Controller feedback [%]
Par. 14.5
Par. 14.6
0 V
0 mA
Custom min
Par. 6.2/6.6
Custom max
Par. 6.3/6.7
10 V
20 mA
Analogue input
with custom
min and max
scaling [%]
Fig. 66. Feedback minimum and maximum
P gain
This parameter defines the gain of the PID controller. If the value of the
parameter is set to 100%, a change of 10% in the error value causes the
controller output to change by 10%.
PID controller I-time
This parameter defines the integration time of the PID controller. If this
parameter is set to 1,00 second, the controller output is changed by a value
corresponding to the output caused from the gaine very second. (Gain × Er-
ror)/s.
PID controller D-time
This parameter defines the derivative time of the PID controller. If this pa-
rameter is set to 1,00 second, a change of 10% in the error value causes the
controller output to change by 10%.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...