Technical Note 

CTTN # 149    

 

This Technical Note is pertinent for Unidrive SP and Unidrive Classic 

 

Quick Setup/Checkout Guide 

 

There are many considerations when setting up a drive of which safety during 
commissioning is of primary concern.  One should always have a method of E-Stopping 
the drive and verify that it works before attempting a drive setup.  This guide is intended 
for the technician who is already familiar with the Unidrive Classic or Unidrive SP and is 
no substitute for the information provided in the User Guides for these products.  It is 
merely a short form guide outlining very basic initial setup steps toward the goal of 
verification of a drive and motor combination.

 

 

Unidrive Classic

      

 

       

Unidrive SP 

 
Enable 

( typically 30-31 ) 

 

                Terminal 22-31 

Security 

#0.00= 149   

 

 

        #0.49=  L2 

Storing/Saving 

      #0.00= 1000  then 

RESET  

( Stop Button )    

Setting Defaults 

      #0.00= 1244  then 

RESET  

( Stop Button ) 

Mode Change 

 #0.00= 1254  then set #0.48= desired mode then 

RESET

 

Normal Display  

         #0.10 shows Motor rpm  

Auto Tune 

 #0.40=1  Rotating   

           #0.40=1 Static  non-rotating) 

       #0.40=2 

Rotating 

 ( motor will go to 2/3 max speed ) 

 

 

            

 

 

Enable needs toggled to move beyond 

 
 ( Shaft must be unloaded for rotating Autotune !!! ) 

 

 

 

  Performing an Autotune – 

Show Me

 

Main Setup Parameters are in Menu 0 

 

#0.02 

   Max 

Hz 

or 

RPM 

#0.03 & 0.04   

 

Accel and Decel rates 

#0.05   

 

 

Basic  Control Method   ie 

Pad

  

(or 4 )

= Keypad operation 

 
#0.42 = # of motor poles 
#0.43 = power factor ( not Service Factor !  Never 1 or greater !! 

 

If you don’t know it leave at 0.85 

Motor 

Namplate 

Data 

#0.44 = rated voltage 
#0.45 = rated RPM

 

#0.46 = rated AMPS

   

#0.47 = rated Frequency 

CTTN149     V1.3

 Page 

1

 5/26/2009 

 

efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor

Содержание Unidrive Classic

Страница 1: ...e typically 30 31 Terminal 22 31 Security 0 00 149 0 49 L2 Storing Saving 0 00 1000 then RESET Stop Button Setting Defaults 0 00 1244 then RESET Stop Button Mode Change 0 00 1254 then set 0 48 desired mode then RESET Normal Display 0 10 shows Motor rpm Auto Tune 0 40 1 Rotating 0 40 1 Static non rotating 0 40 2 Rotating motor will go to 2 3 max speed Enable needs toggled to move beyond Shaft must ...

Страница 2: ...lection CTVI104 Modifying Numeric Values CTVI105 Saving Parameter Changes CTVI106 Saving drive data on SMARTCARD CTVI107 Read drive data from SMARTCARD CTVI108 Accessing parameters outside menu 0 AC Motor Synchronous Speeds Poles 50Hz Motor 60Hz Motor 2 3000 3600 4 1500 1800 6 1000 900 8 750 450 Example If a motors nameplate indicates that its rated speed is 3510 rpm this would infer that the moto...

Страница 3: ...or is not necessary 3 0 08 3 for motor 30HP and less 1 for motors 40HP 75HP 0 3 for motors 100HP 200HP 4 Recheck motor parameters 0 42 0 47 and Max Hz 0 02 60Hz 5 Accel Rates 0 03 0 04 5 15 5 seconds to 100Hz Use larger values for large motors inertias Also turn S ramp 2 06 On The amount of S curvature could also be increased with 2 07 6 You should be able to run drive from keypad for basic checko...

Страница 4: ...motor shaft clockwise will result in up counting if not swap A and A Check for correct encoder PPR 3 21 3 34 Unidrive Classic Unidrive SP If correct Encoder 3 27 3 29 Rev 4096 16384 Rev 8192 32767 1 Rev 16384 65 535 You could run Auto Tune Auto Tune 0 40 1 Rotating 0 40 1 Static non rotating 0 40 2 Rotating motor will go to 2 3 max speed Enable needs toggled to move beyond Shaft must be unloaded f...

Страница 5: ...ap A and A Check for correct encoder PPR 3 21 3 34 Unidrive Classic Unidrive SP If correct Encoder 3 27 3 29 Rev 4096 16384 Rev 8192 32767 1 Rev 16384 65 535 You could run Auto Tune Auto Tune 0 40 1 Rotating 0 40 1 motor rotates upto 2 revs 0 40 2 motor rotates upto 2 revs Stator resistance measured in test 2 Parameter 3 25 gets updated with motor phasing angle Enable needs toggled to move beyond ...

Страница 6: ...verse 2 motor leads U and V Vector Mode Reverse 2 motor leads U and V And Swap A and A encoder wires cheap and dirty method Correct method would be to swap A with B and A with B Servo Mode Reverse 2 motor leads U and V And Swap A and A encoder wires cheap and dirty method Correct method would be to swap A with B and A with B And Swap U with V and U with V on encoder CTTN149 V1 3 Page 6 5 26 2009 e...

Отзывы: