Vector Mode 

 

If drive is setup for CL.Vector  ( see 0.48 ) then the drive can be run and checked 
for  its’ most basic operation.

 

 

Set  

 

#0.05 = 

Pad

 (or 4 ) 

so that you can Start/Stop and change speed from front of drive 

 
Recheck motor parameters #0.42 - 0.47 and Max RPM  (# 0.02 ) ,  
Accel Rates #0.03 & 0.04   = 5-15 seconds to 1000rpm 
S-ramp    #2.06 = On     S-Curvature    #2.07  could be increased a bit ( 10 ) 
Stop Mode   

rP 

=    Ramp       located at    #6.01 in both Classic & SP 

 
Verify encoder voltage   

Unidrive Classic

      

 

       

Unidrive SP 

#3.23      0= 5v    1= 15v                           #3.36     5,8,15v 

 

 

 

 

 

                    If >5v set #3.39= 0 

 
Check for proper encoder wiring and operation    
 

Manual rotation of motor shaft clockwise will result in up counting    

 

                                   –if not swap A and /A 

Check for correct encoder PPR   #3.21   

 

 

 

#3.34 

  Unidrive Classic

    

 

 

       

Unidrive SP 

If correct 

Encoder 

 #3.27=    

 

 

 

  

       #3.29=   

 

¼ Rev  

         =   4096 

 

 

 

     =   16384 

½ Rev  

         =   8192 

 

 

 

     =   32767 

1  Rev  

         =   16384 

 

 

 

     =   65,535 

 
You could run Auto Tune 
Auto Tune 

 

#0.40=1  Rotating   

#0.40=1 Static  ( non-rotating) 

       #0.40=2 

 

 

 

 

Rotating 

      ( motor will go to 2/3 max speed ) 

 
 

 

            

 

 

  Enable needs toggled to move beyond 

 ( Shaft must be unloaded for rotating Autotune !!! ) 

 
If motor rotates CCW  reverse  U & V motor leads and repeat 
 
You should be able to run drive from keypad for basic checkout. 
Test by depressing 

GREEN

 Run and Up Arrow to ¼ speed then test 

Stop

 

If ok go to ½ Speed – Stop  then ¾ - Stop  then to Full Max Speed if all OK

CTTN149     V1.3

 Page 

4

 5/26/2009 

 

efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor

Содержание Unidrive Classic

Страница 1: ...e typically 30 31 Terminal 22 31 Security 0 00 149 0 49 L2 Storing Saving 0 00 1000 then RESET Stop Button Setting Defaults 0 00 1244 then RESET Stop Button Mode Change 0 00 1254 then set 0 48 desired mode then RESET Normal Display 0 10 shows Motor rpm Auto Tune 0 40 1 Rotating 0 40 1 Static non rotating 0 40 2 Rotating motor will go to 2 3 max speed Enable needs toggled to move beyond Shaft must ...

Страница 2: ...lection CTVI104 Modifying Numeric Values CTVI105 Saving Parameter Changes CTVI106 Saving drive data on SMARTCARD CTVI107 Read drive data from SMARTCARD CTVI108 Accessing parameters outside menu 0 AC Motor Synchronous Speeds Poles 50Hz Motor 60Hz Motor 2 3000 3600 4 1500 1800 6 1000 900 8 750 450 Example If a motors nameplate indicates that its rated speed is 3510 rpm this would infer that the moto...

Страница 3: ...or is not necessary 3 0 08 3 for motor 30HP and less 1 for motors 40HP 75HP 0 3 for motors 100HP 200HP 4 Recheck motor parameters 0 42 0 47 and Max Hz 0 02 60Hz 5 Accel Rates 0 03 0 04 5 15 5 seconds to 100Hz Use larger values for large motors inertias Also turn S ramp 2 06 On The amount of S curvature could also be increased with 2 07 6 You should be able to run drive from keypad for basic checko...

Страница 4: ...motor shaft clockwise will result in up counting if not swap A and A Check for correct encoder PPR 3 21 3 34 Unidrive Classic Unidrive SP If correct Encoder 3 27 3 29 Rev 4096 16384 Rev 8192 32767 1 Rev 16384 65 535 You could run Auto Tune Auto Tune 0 40 1 Rotating 0 40 1 Static non rotating 0 40 2 Rotating motor will go to 2 3 max speed Enable needs toggled to move beyond Shaft must be unloaded f...

Страница 5: ...ap A and A Check for correct encoder PPR 3 21 3 34 Unidrive Classic Unidrive SP If correct Encoder 3 27 3 29 Rev 4096 16384 Rev 8192 32767 1 Rev 16384 65 535 You could run Auto Tune Auto Tune 0 40 1 Rotating 0 40 1 motor rotates upto 2 revs 0 40 2 motor rotates upto 2 revs Stator resistance measured in test 2 Parameter 3 25 gets updated with motor phasing angle Enable needs toggled to move beyond ...

Страница 6: ...verse 2 motor leads U and V Vector Mode Reverse 2 motor leads U and V And Swap A and A encoder wires cheap and dirty method Correct method would be to swap A with B and A with B Servo Mode Reverse 2 motor leads U and V And Swap A and A encoder wires cheap and dirty method Correct method would be to swap A with B and A with B And Swap U with V and U with V on encoder CTTN149 V1 3 Page 6 5 26 2009 e...

Отзывы: