Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
82
Table 33. Protections.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P12.13 Stall frequency
0,10
320,0
Hz
25,00
712
P12.14 Field weakening load
10,0
150,0
%
50,0
714
P12.15 Zero freq load
5,0
150,0
%
10,0
715
P12.16 Time limit
1,0
300,0
s
20,0
716
P12.17 Analogue Input low fault
delay
0,0
10,0
s
0,5
1430
P12.18 External fault
0
3
2
701
As parameter 12.3
P12.19 Fieldbus fault
0
4
3
733
As parameter 12.1
P12.20 Preset alarm frequency
P3.1
P3.2
Hz
25,00
183
P12.21 Parameters edit lock
0
1
0
819
0 = Edit enabled
1
= Edit disabled
P12.22 Thermistor Fault
0
3
2
732
Hidden until option board supporting
thermistor is connected:
0 = No action
1
= Alarm
2
= Fault: Stop function
3
= Fault: Coast
P12.23 FWD/REV conflict supervi-
sion
0
3
1
1463
As parameter 12.3
P12.24 Temperature fault
0
3
0
740
As parameter P12.3, hidden until an
OPTBH board is connected.
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...