Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
43
Table 18. DI Sink Type, remove jumper J500 and connect the wire using this table
Terminal
Signal
Factory preset
Description
3 GND
I/O signal ground
6 24 Vout
24 V output for DI's
±20%, max. load 50 mA
7 DI_C
Digital Input Common
Digital Input Common for DI1-DI6
8 DI1
Digital input 1
Start forward
P)
Positive Logic 1: 18…+30 V,
Positive Logic 0: 0…5 V;
Negative Logic 1: 0…10 V,
Negative Logic 0: 18…30 V;
Ri = 10 k
Ω
(floating)
9 DI2
Digital input 2
Start reverse
P)
10 DI3
Digital input 3
Fault reset
P)
14 DI4
Digital input 4
Positive Logic 1: 18…+30 V,
Positive Logic 0: 0…5 V;
Negative Logic 1: 0…10 V,
Negative Logic 0: 18…30 V;
Ri = 10 k
Ω
(floating)
15 DI5
Digital input 5
Only for DI.
16 DI6
Digital input 6
Only for DI.
P) = Programmable function, see parameter lists and descriptions, Chapters „9
Standard application parameters“ on page 55 and „10
Parameter description“ on page 96.
ON
S1
S2
S3
S4
J500
OFF
ON
OFF
ON
OFF
ON
OFF
DI Encoder *
AO - V mA
A12 - V mA
RS-485 - Term
* Logic input configured as encoder input. Not used.
Must leave at default
Fig. 35. Microswitches
4
5
13
14
15
16
20
18
1
2
3
6
7
8
9
10
22
23
26
24
25
AI2 GND DO- DI4 DI5 DI6 AO DO+
RO1
NO
RO1
CM
*
RO2
NO
+10VAI1 GND 24V DI-C DI1 DI2 DI3
A
B
RO2
CM
RO2
NC
Figure 36. HVAC232/402 I/O terminals:
Содержание HVAC232 Series
Страница 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Страница 19: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 19 MI1 MI5 3P 400 V POWER LOSS ...
Страница 20: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 20 MI1 MI5 3P 400 V POWER LOSS ...
Страница 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Страница 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Страница 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...