![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 98](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379098.webp)
4 Control system
Printed circuit board for complementary systems
SMGB0137 rev.0 - 05/2021
88
4.10 Printed circuit board for complementary systems
4.10.1 Printed circuit board for KPI (PI073)
FUSE
PCB1
PCB2
PCB1 LED indicator
LED1
Red
This LED indicates the transmission
status between the indoor unit and the
remote control.
LED3
Yellow
This LED indicates the transmission
status between the indoor unit and the
outdoor unit.
LED4
Green
PCB power supply
PCB2 LED indicator
LED1
Yellow
H-LINK transmission external
LED2
Green
PCB power supply
LED3
Yellow
H-LINK transmission internal (between
PCBs)
PCB1 Connector indication
PCN1
230V transformer
PCN2
Bridge
PCN3
Auxiliary heater
PCN7
Terminal board 1 (TB1)
PCN10
Motor for Damper
THM1
Air inlet thermistor
THM2
Outlet air thermistor
THM3
Liquid pipe thermistor (KPI-X3E only)
THM4
Optional connector (for remote temperature sensor
to control an auxiliary heater)
THM5
Gas pipe thermistor (KPI-X3E only)
CN1
Transformer 12V
CN2
TB1 and PCB2
CN11
Expansion valve (KPI-X3E only)
CN14
Flow switch (KPI-X3E only)
EFR1
Power supply fuse
EF2
PCB fuse
EF3
Fuse for PCN5 connector
PCB2 Connector indication
PCN1
TB1 and PCB1
THM1
Coil inlet thermistor (KPI-X3E only)
THM2
Coil outlet thermistor (KPI-X3E only)
CN1
TB2 and PCB1
CN2
CO
2
sensor 4-20 mA
CN3
CO
2
sensor 0-10 V
CN4
CO
2
sensor ON/OFF
CN5
Motor for fan 1
CN6
Motor for fan 2
EF1
PCB2 fuse
Switch indication
DSW3
Capacity code
DSW4
Unit model code
DSW5,
RSW2
Refrigerant cycle number setting
DSW6,
RSW1
Indoor unit number setting
DSW7
Fuse recovery