5 Optional functions
Indoor units input and output signals
SMGB0137 rev.0 - 05/2021
106
Heating operation signal
On-screen display: 05.
This optional signal is used to pick up the heating operation signal. An example of basic wiring is shown below.
The contact of the auxiliary relay “RYa” is closed when this operation signal is given.
Connect the wiring and use the materials as indicated in
. (Example: terminal 1 and 3 of CN7).
CN7
RYa
1
3
RY
3P Connector
CN7 Connector
Indoor unit PCB
Auxiliary relay
Heating operation output is set to terminals 1 and 3 of CN7
Thermostat enabled signal during the heating process
On-screen display: 06.
This optional signal is used to pick up the thermostat enabled signal for the compressor operating (Thermo-ON) during
the heating process and to control, for example, a circulation pump or humidifier.
Connect the wiring and use the materials as indicated in
. (Example: terminals 1 and 2 of CN8).
The contact of the auxiliary relay “RYa” is closed during Thermo-ON in the heating operation.
RY
CN8
1
2
RYa
3P Connector
CN7 Connector
Indoor unit PCB
Auxiliary relay
Heating Thermo-ON output is set to terminals 1 and 2 of CN8
Total heat exchanger signal
On-screen display: 07.
This function is utilized to pick up the total heat exchanger signal during the ventilation mode selected with a wired
controller. An example of basic wiring is shown below.
CN7
RYa
1
3
RY
3P Connector
CN7 Connector
Indoor unit PCB
Auxiliary relay
Total heat exchanger output is set to terminals 1 and 3 of CN7