5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
117
5
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
Fd
Upper limit of setting
temperature for heating
(Maximum value of setting
temperature allowed in
heating)
X
00
Function disabled
30 ºC is the standard maximum set
point. (factory setting)
This function defines the highest
temperature setting value for
HEATING mode.
Models:
RPF(I)-FSN2E
up to 20ºC (FC=10)
01
-1 ºC (Upper limit 29 ºC)
02
-2 ºC (Upper limit 28 ºC)
03
-3 ºC (Upper limit 27 ºC)
·
·
·
·
·
·
10
-10 ºC (Upper limit 20 ºC)
11
-11 ºC (Upper limit 19 ºC)
12
-12 ºC (Upper limit 18 ºC)
FE
Not used
-
00
-
Use at 00 conditions
01
02
FF
Not Used
O
00
-
Use at 00 conditions
01
H1
No indication of
maintenance alarm
–
00
Displayed
This function is used to display
or hide the maintenance alarm
indication.
01
Hidden
H2
Indication of hot start
(No Indication of operation
limitation)
X
00
Displayed
This function is used to display
or hide the automatic control
indication.
Models:
RPF(I)-FSN2E
Not available, use at 00
conditions
01
Hidden
H3
Not used
–
00
-
Use at 00 conditions
01 / 02
H4
Not Used
–
00
-
Use at 00 conditions
01
-
KPI: Operation modes for
the ventilation unit with
energy recovery
O
00
Air conditioning only
(factory setting)
This function is only available
for ventilation units with energy
recovery.
01
Ventilation only
02
Air condit ventilation
J1
Not used
-
00
-
Use at 00 conditions
01
J2
Not used
-
00
-
Use at 00 conditions
01
J3
Colour of the Run
indicator
X
00
Green (factory setting)
–
01
Red
J4
Override of Start/Stop
prohibition at the remote
controller
X
00
Start/Stop allowed (Factory setting)
When there is a remote control
prohibition from a central control
device, this function overrides
this prohibition allowing the
operation of the Run/Stop button
of the remote control switch.
Models:
RPF(I)-FSN2E
Not used. Use at 00 conditions
01
Start/Stop not allowed
!
D A N G E R
Blocking of Start/Stop shall never
be set due to safety concerns.
02
Only Stop allowed