2 Optional accessories
Duct adapter - Outdoor air inlet
SMGB0137 rev.0 - 05/2021
20
2.1 Duct adapter - Outdoor air inlet
2.1.1 For RCI-FSR indoor units: OACI-160K2 and PD-75A
The inlet of outdoor air is possible through the PD-75A or the OACI-160K2 duct connection in the position shown in the
figure. (Sold separately).
OACI-160K2
PD-75A
(*)
(**)
(*) 1 or 2 duct adapter can be installed
(**) Only 1 duct adapter can be installed
Outdoor air inlet duct connection position
This kit can not supply the fresh air by itself. Therefore,
connect the duct and supply the fresh air from the total heat
exchanger or the duct fan.
When connecting this kit to the total heat exchanger or the
duct fan, make an interlock to the fan of the indoor unit.
The example is shown below.
Use a cable with a three-terminal connector (PCC-1A) for
the CN7 connector on the indoor PCB.
CN7
1
2
RY
52F
AC
RYa
Indoor Unit Printed Circuit Board
Total Heat Exchanger
or Magnetic Switch
Auxiliary Relay
Total heat exchanger
or magnetic switch
Indoor unit printed circuit board
Auxiliary relay
Remarks for OACI-160K2
The standard maximum air volume of fresh air intake when using the outdoor air inlet duct reference OACI-160K2
combined with a total heat exchanger or the duct fan, is within 20% of the rated air volume of the indoor unit (at “HIGH”
mode). If the amount of incoming outdoor air exceeds this value, condensation may be produced on the inner surface of
the drain pan (air inlet hole) and, in some cases, dew may form.
In the case without total heat exchanger, use the fresh air intake kit within the range which dewing does not occur at this
kit, duct and inside the indoor unit.
With or without the total heat exchanger, follow the countermeasure according to the temperature difference between the
supply air from the room air and the outside air as shown in the table below.
Temperature difference between supply air from room air
and outside air
Countermeasure
Below 10 degree
No countermeasure required
Below 15 degree
Perform insulation
Over 15 degree
Use with total heat exchanger or
Operation is not permissible.