![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 195](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379195.webp)
7 Servicing
RCI-(1.0-6.0)FSR - 4-way cassette
SMGB0137 rev.0 - 05/2021
185
7
7.1.5
Removing printed circuit board (PCB1)
1
Remove the air inlet grille according to the item
“7.1.1 Removing air filter and air inlet grille”
2
Remove the electrical box according to the item
“7.1.2 Removing electrical box cover”
.
3
Disconnect all wiring connectors from PCB1.
4
Remove the screw for earth wire.
5
The PCB1 is fixed by six (6) holders. Bend the holders
B
by finger and raise the PCB1. Remove the PCB1 from the
holders
A
by drawing it towards arrow direction in the figure below.
Indoor Unit PCB
Electrical Box
Holder B
Screw for
Earth Wire
PCB1
PCB1
Holder
Bend the holder by finger.
Holder A
Holder
Screw for
earth wire
Electrical box
Holder
Holder
Bend the holder by finger
Indoor unit PCB
?
N O T E
•
Do not touch electrical parts on PCB1.
• Pay attention not to apply an excessive force to PCB1. It may cause failure of PCB1.
• When reassembling, attach connectors to the correct position. If not, the PCB1 may be damaged. In addition, securely attach the
screw for earth wire.