5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
109
5
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
C5
Static pressure selection
Models
RPI(L/H)-FSRE
RPI-FSN3(P)E(-f)
O
00
Standard static pressure
(factory setting)
This function is used to change
the static pressure of the RPI
units from the remote control.
01
High static pressure
02
Low static pressure
Increase of fan speed
during normal operation
(not during heating
Thermo-OFF)
Models
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPK-FSR(H)M
RPF(I)-FSN2E
O
00
Standard
(factory setting)
This function is used to change
the fan speed of indoor units
installed in high ceilings.
01
Hi Speed 1
02
Hi Speed 2
Fan speed setting on the remote controller
C5
High H
High
Medium
Low
0
Hi2
Hi
Me
Lo
1
Hi2
Hi1
Hi
Me
2
Hi2
Hi2
Hi1
Hi
(This function C5 is not available for DX-Interface models)
C6
Increase of fan speed at
heating Thermo-OFF
(Not available for models
KPI-E4 and KPI-X4E)
O
00
Function disabled
(factory setting)
This function is used to
increase the fan speed when
the thermostat reaches the
set temperature in heating
according to the setting of
function C5.
01
Function enabled
C7
Cancellation of forced
compressor operation for
at least 3 minutes
O
00
Function disabled
(factory setting)
This function is available
depending on the setting of
function b3.
01
Function enabled
(Compressor operation during 3
minutes is no longer forced)
Only for KPI-E4E and
KPI-X4E
CO
2
sensor enabled
00
Sensor non enabled
(factory setting)
Via 7-segments display set the
option
Ct
(00: ON/OFF Sensor
(Default); 01: 4-20mA 02: 0-10V)
01
Sensor enabled/activated