7.3.11
Removal of the automatic louver motor
1
Stop the automatic louver:
a.
Press AUTO LOUVER on the remote control while the automatic louver is operating.
b. The crank (2) touches the end of the motor securing plate (7) and the louver returns to position 0.
c.
The motor (1) power supply switches off when the louver is at the set position.
d. The louver (6) stops at the set position.
2
Remove the air panel according to the item
“7.1.3 Removing optional air panel”
3
Remove the fixing screw for C-cover and remove the C-cover.
C-Cover
C-Cover
Screw
Screw
4
Peel off the off the panel rib for the sealing gasket the remove
the guide.
5
Pull the guide upwards and remove it.
Guide
6
Disconnect the connector from the AS motor.
7
Remove two fixing screws for AS motor from the air panel. Then remove the louver and AS motor form the air panel.
8
Remove the louver from the bearing for AS motor.
Louver
Bearing
AS Motor
Screw
Screw
AS Motor