7.5
RPI(L/H)-(0.4-6.0)FSRE - Ducted indoor unit
7.5.1
Removal of the electrical box
The design of the new electrical box allows it to be separated from the RPIL-(0.4-1.5)FSRE and RPI-(1.5-2.0)FSRE for
independent installation. The electrical box is located on the left side, but it can be moved to the right side and even
fixed directly to the wall. In this way, it is easier to take advantage of the spaces available for mounting the system and
facilitate maintenance and possible operations.
In order to change the source configuration (mounted on the left side), the following steps must be followed:
1
Loosen and remove the 2 screws at the bottom of the cover, of the electrical box.
2
Loosen and remove the 2 screws that hold the electrical box to the indoor unit.
3
Tilt the electrical box forward so that the flanges holding the electrical hose can be cut.
α
α
= 15
°