![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 278](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379278.webp)
7 Servicing
RPF(I)-(1.0-2.5)FSN2E - Floor and Floor concealed type
SMGB0137 rev.0 - 05/2021
268
7.8.4
Removal of the front panel
1
Remove the central panel air filter in line with the instructions
“7.8.2 Removal of the air filter”
2
Remove the screws from the lower part of the front panel.
?
N O T E
• RPF-(1.0-2.5)FSN2E: 4 screws.
• RPFI-1.0FSN2E: 9 screws.
• RPFI-1.5FSN2E: 10 screws.
Front
panel
Screw
Screw
3
Remove the 11 set screws and remove the front panel.
Front lower panel
7.8.5
Removal of the fan motor
1
Remove the air inlet grille as indicated in chapter
“7.8.1 Removal of the air inlet grille”
.
2
Remove the air filter as indicated in section
“7.8.2 Removal of the air filter”
3
Remove the four set screws from the fan motor assembly plate and remove it.
4
Disconnect the wiring from the fan motor connector. Remove the wiring board and the connector.
5
Remove the cover by pressing the four attachment points inwards.
6
Loosen the bolts using a wrench.
7
Remove the securing plate.
8
Remove the fan motor by sliding it backwards.
?
N O T E
Be careful when releasing the fan motor, as it could fall.