5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
115
5
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
F1
Automatic OFF timer
setting
Models:
RCI-FSR
RPC-FSR
RPK-FSRM
RPI(L/H)-FSRE
RCD-FSR
RCIM-FSRE
RPI-FSN3(P)E
X
00
Function disabled
(Factory setting)
This function sets an automatic
OFF timer to switch OFF the
indoor units controlled by the
remote control switch (when
the units have been started by
remote control).
(Do not set the values "0C"-
"0F" when two remote control
switches are used in the same
remote control group)
01
1 hour
02
2 hours
03
3 hours
04-24
(04-24) hours
0A
30 minutes
0B
90 minutes
0C
40 minutes
}
Do not set these
when two wired
controllers are
used.
0D
45 minutes
0E
50 minutes
0F
55 minutes
Automatic OFF timer
setting
Models:
RPF(I)-FSN2E
X
00
Function disabled
(Factory setting)
This function is used to set the
automatic timer to switch off
when the unit has been started
by remote control.
01
1 hour
02
2 hours
03
3 hours
04-24
(04-24) hours
0A
30 minutes
0B
90 minutes
F2
Remote control main-sub
setting
X
00
Main (Master remote control)
(Factory setting)
This function is used to define
which remote control switch is
used as master or slave, when
two remote controllers are
connected to one indoor unit.
01
Sub (Slave remote control)
F3
Automatic reset of setting
temperature
X
00
Function disabled
(Factory setting)
This function is used to limit unit
operation and save energy.
The setting temperature is
automatically set to the value
defined with functions "F5" or
"F6", according to the current
operation mode, after the time
set with function "F4" has
passed since the last manual
change of setting temperature.
In case that the values of "F5"
or "F6" are out of the limits set
with functions "FC" and "Fd",
limitations set by "FC" and "Fd"
have priority.
01
Function enabled
F4
Automatic reset time
X
00
30 minutes (factory setting)
This function sets the automatic
reset time delay for function F3.
01
15 minutes
02
60 minutes
03
90 minutes