5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
113
5
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
E1
KPI: Ventilation mode
O
00
Automatic ventilation
(factory setting)
This function allows the outdoor
air damper to be opened in
All Fresh operation mode. This
mode allows the full opening
of the outdoor air damper
(according to the control
system).
01
Ventilation with total heat exchanger
02
Ventilation with bypass (no total heat
exchange)
DX-Interface:
“A” Offset for Thermo-OFF
in control by outlet for DX-
Interface
00
Disabled (factory setting)
01
2 ºC
02
4 ºC
Econofresh: cooling mode
00
Standard process
(factory setting)
This function allows the outdoor
air damper to be opened in
All Fresh operation mode. This
mode allows to fully open the
outdoor air damper (according to
the control system).
01/02
All Fresh
E2
KPI: Increase of air supply
volume
O
00
Disabled function
(factory setting)
This function is used to make
the room pressure higher or
lower than the surrounded
room. One of the fans increases
its speed while the other runs
according the remote controller.
Hi/Me/Lo change to Hi/Hi/Me
01
Enabled function
Econofresh enthalpy
sensor
00
Disabled function
(factory setting)
This function selects the
enthalpy sensor input for
Econofresh.
01
Enabled function
E3
Not used
–
00
-
Use at 00 conditions
01
Only for KPI-E4E and
KPI-X4E:
Selection of the fan for
function E2
–
00
Activated for supply fan
This function selects which fan
will increase the speed (when
E2 enables this function).
01
Activated for exhaust fan
E4
KPI: Pre-cooling / pre-
heating period
O
00
Disabled (factory setting)
This function delays unit startup
with energy recovery.
01
30 minutes
02
60 minutes
Econofresh: CO
2
sensor
00
Disabled (factory setting)
This function selects the CO
2
gas sensor input for Econofresh.
01/02
CO
2
sensor
(required setting E1=00)
E5
Not used
–
00
-
Use at 00 conditions
01
Only for DX-Interface,
KPI-E4E and KPI-X4E:
High ventilation after
switch ON
–
00
Disabled (factory setting)
This function forces that the unit
will operate in high speed during
60 minutes after fan start. After
this time the fan will be changed
to setting value.
01
60 minutes
E6
Period of indoor fan
operation after cooling
operation stoppage
O
00
Disabled function
(factory setting)
This function prevents the
condensation in the unit by
keeping the fan running after the
unit operation has been turned
OFF.
01
60 minutes
02
120 minutes
E7
Not used
–
00
-
Use at 00 conditions
01