![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 197](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379197.webp)
7 Servicing
RCI-(1.0-6.0)FSR - 4-way cassette
SMGB0137 rev.0 - 05/2021
187
7
7.1.8
Removing drain-up mechanism
1
Remove the drain pan according to the item
2
Remove the insulation which attaches the wires for float switch and drain-up mechanism together.
3
Cut the plastic band fixing the wires at the fixing plate for float switch.
4
Cut the hose band for drain hose by nipper, and remove the drain hose from the drain-up mechanism.
5
Remove two (2) fixing screws for drain-up mechanism. When removing, hold the drain-up mechanism by hand in
order not to fall.
6
Remove the drain-up mechanism.
?
N O T E
When reassembling, wrap up the wires for float switch and drain-up mechanism together by the insulation Fix securely them to the
original position. When attaching the drain pan again, pay attention not to pull the wires strongly. Otherwise, the insulation attaching
at the cabinet may be peeled.
P
Wiring
Fixing screws
Float switch
Drain-up mechanism
Hose band
Drain hose
Nut
Fixing plate for
float switch
Plastic band
Lead wires
Screw for fixing
plate
VIEW FROM P