7 Servicing
RPI(L/H)-(0.4-6.0)FSRE - Ducted indoor unit
SMGB0137 rev.0 - 05/2021
230
RPI-(2.5-6.0)FSRE and RPIH-(4.0-6.0)FSRE
1
Remove the motor cover as explained in
“7.5.4 Removal of the motor cover”
.
2
Remove the casing screws (4 screws in each casing assy).
3
Press the locks and remove half of the fan casing.
4
Remove the motor support screws.
5
Loosen 4 fixing screws for the fan runner with a hexagon wrench and remove the fan runner from the motor shaft.
6
Remove the runner from the casing.
7
Then remove the fan motor.
?
N O T E
If the fan casing is to be fully removed, remove the screws securing the other half to the fan motor fixture.
Locks
Locks
Motor support screws
Casing screw
Casing screw
Bottom side
RPI-(2.5-6.0)FSRE
Locks
Locks
Motor support screws
Casing screw
Casing screw
Bottom side
RPIH-(4.0-6.0)FSRE