6 Commissioning
Test run check list
SMGB0137 rev.0 - 05/2021
178
6.3 Test run check list
MODEL:
SERIAL NUMBER
COMPRESSOR MFG NO
NAME AND ADDRESS OF CUSTOMER:
DATE:
1 Does the indoor unit fan turn in the correct direction? __________
2 Has the unit been running for at least twenty (20) minutes? __________
3 Check the temperature of the room:
Inlet:
Nº 1
DB/WB _____ºC
Nº 2
DB/WB _____ºC
Nº 3
DB/WB _____ºC
Nº 4
DB/WB _____ºC
Outlet:
DB/WB _____ºC
DB/WB _____ºC
DB/WB _____ºC
DB/WB _____ºC
Inlet:
Nº 5
DB/WB _____ºC
Nº 6
DB/WB _____ºC
Nº 7
DB/WB _____ºC
Nº 8
DB/WB _____ºC
Outlet:
DB/WB _____ºC
DB/WB _____ºC
DB/WB _____ºC
DB/WB _____ºC
4 Check the outside temperature:
Inlet
DB/WB _____ºC
Outlet
DB/WB _____ºC
5 Check the temperature of the refrigerant: Operating mode (cooling or heating).
Discharge gas temperature
Td = _____ºC
Liquid pipe temperature
Te = _____ºC
6 Check the pressure:
Discharge pressure
Pd = _____kg/cm
2
G
Suction pressure
Ps = kg/cm
2
G
7 Check the voltage:
Rated voltage
_____V
—
—
Service voltage
L1–L2 _____V
L1–L3 _____V
L2–L3 _____V
Initial voltage
_____V
—
—
Phase imbalance
1-(V/Vm) =
—
—
8 Check the compressor inlet operating current
Inlet
_____kW
Suction pressure
_____kW
9 Is the refrigerant charge OK? __________
10 Do the operating control devices work properly? __________
11 Do the safety devices work correctly? __________
12 Has the unit been checked for refrigerant leaks? __________
13 Is the unit clean? __________
14 Are all the panels of the unit fastened securely? __________
15 Are the panels of the cabinet fastened so that they do not make any noise? __________
16
Is the filter clean? __________
17 Is the heat exchanger clean? __________
18 Are the stop valves open? __________
19
Does the water flow freely through the drainage pipe? __________