5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
145
5
Item
Optional function
Individual
Setting
Settings
Setting conditions
Description
Cg
Not available
-
“- -”
permanent –
–
CA
Not available
-
“- -”
permanent –
–
Cb
Selection of forced
stoppage logic
○
00
Forced stoppage input: A contact,
normally open contact (factory
setting)
This function determines the logic
operation for the forced stoppage
contacts.
01
Forced stoppage input: B contact,
normally closed contact
CC
Not used
–
00
-
Use at 00 conditions
01
Only for
DX-Interface,
KPI-E4E and
KPI-X4E
High ventilation
speed
00
Function disabled
(factory setting)
This function sets the unit to run
in high fan speed regardless the
setting from remote control switch.
01
Function enabled
Cd
Stop of indoor unit
fan during cooling
Thermo-OFF
conditions
?
N O T E
For model
RPI-FSN3E(P)
E and RCD-FSR,
this function is NOT
available.
-
00
Fan speed during cooling
Thermo-OFF: Low (factory setting)
The operation of the indoor unit fan
is stopped in cooling Thermo-OFF
conditions when using the additional
remote temperature sensor
THM-R2AE (connected to THM4)
or the PC-ARFP1E temperature
sensor.
C8 must be set to 01 to use the
Cd=01 setting.
01
Indoor unit fan is stopped during
cooling Thermo-OFF
CE
Stop of indoor unit
fan during heating
Thermo-OFF
conditions
Stop of indoor unit
fan during heating
Thermo-OFF
conditions (with
remote control
switch temperature
sensor)
-
00
Fan speed setting during heating
Thermo-OFF: Low (factory setting)
The indoor unit uses the
PC-ARFP1E temperature sensor to
monitor the room temperature when
the fan is stopped (heating
Thermo-OFF fan stop sequence)
C8 must be set to 01 to use the
CE=01 setting.
Control by remote temperature
sensor connected to THM4 is not
permitted (use E8 function in that
case).
01
Indoor unit fan is stopped during
heating Thermo-OFF.
(In case that automatic louvre is set,
the louvres will keep operating in
both Thermo-ON and Thermo-OFF
conditions)
CF
Modification of
louvre swing range
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
○
00
Standard (7 steps)
(factory setting)
This function adjusts the angle of the
air outlet louvre.
(Changes to the setting of this
function are applied after turning the
power supply off and on again, or
after the automatic louvre has made
a full cycle in automatic mode)
01
Cold draft prevention (5 steps)
(Cannot be set to the lower two
steps; lower 2 steps cut off)
02
High ceilings (5 steps)
(Cannot be set the upper two steps;
upper 2 steps cut off)
Models:
RPK-FSR(H)M
○
00
Standard (7 steps)
(5 steps for cooling / dry mode)
01
Cold draft prevention
(5 steps for heating and fan only)
(Cannot be set to the lower two
steps, lower 2 steps cut off)
02
Not used