![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 122](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379122.webp)
5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
112
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
d4
Prevention of low air
outlet temperature in
cooling mode
Models:
RPI-(4.0-6.0)FSRE
O
00
Function disabled
(factory setting)
This function is used to prevent
the decrease of discharge
air temperature in cooling
operation, by controlling
Thermo-ON/OFF according to
the discharge air temperature.
When ambient temperature >
setting temperature:
If air outlet temperature ≤ 11 ºC
for 3 minutes, the system is
switched to Thermo-OFF.
In this status, if air outlet
temperature ≥ 13 ºC, the system
is switched back to Thermo-ON.
01
Function enabled
Not used
Models:
RCD-FSR
RPI-(0.4-3.0)FSRE
RCI-FSR
RPC-FSR
RCIM-FSRE
RPF(I)-FSN2E
RPI-(8~20)FSN3(P)E
O
00
-
Use at 00 conditions
01
d5
Prevention of low air
outlet temperature in
heating mode
O
00
Function disabled
(factory setting)
This function prevents the
occurrence of an excessively
cold air flow in heating mode
by decreasing the fan speed
during heating operation, also
taking into account the setting of
function C5.
01
Function enabled
d6
Room temperature control
for energy saving
O
00
Function disabled
(factory setting)
This function saves energy
when the outdoor temperature
is lower than the air conditioning
load.
The indoor unit is set to cooling
Thermo-OFF when:
Tout (outside ambient
temperature - out of the building)
< Tin
01
Function activated
d7
Econofresh: Minimum
opening angle of the
outdoor air (OA) damper
O
00
6º (factory setting)
This function is used to set the
minimum opening angle of the
damper for fresh outdoor air.
01
12º
02
18º
03
24º
04
30º
05
36º
06
42º
07
48º