5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
130
d1 – Power supply ON/OFF 1 (Automatic Operation when Power Supply is ON)
This function stores the unit settings in the event of a power cut. The unit is restarted when the power is re-established.
?
C A U T I O N
When this function is used without anyone controlling the unit, set the system monitoring mode to avoid risks.
?
N O T E
In the event of an electrical fault, the unit starts and stops according to the on/off setting of the power supply. If the fault occurs during a
stoppage enabled through the remote control, the unit will restart automatically once the power supply is reconnected.
d2 – Not available
d3 – Power supply ON/OFF 2 (Restarting Function After Power Failure)
This function is used to restart the unit after a power cut taking more than 2 seconds. The standard unit starts
automatically under the same operating conditions, such as the operating mode, etc. in the case of an electrical fault
lasting for a maximum of 2 seconds.
The compressor unit restarts after 3 minutes plus the maximum 2 seconds of the fault.
?
C A U T I O N
When this function is used without anyone controlling the unit, set the system monitoring mode to avoid risks.
d4 – Prevention of drop of discharge temperature in cooling
This function is avoiding getting a too low air outlet temperature from indoor units in cooling operation. Remote Control
Switch is controlling the air outlet temperature and adjusting the Thermo-ON/OFF status accordingly.
When ambient temperature > setting temperature:
-
If air outlet temperature ≤ 11 ºC for 3 minutes, the system is switched to Thermo-OFF.
-
In this status, if air outlet temperature ≥ 13 ºC, the system is switched back to Thermo-ON.
This optional function is only available for the following indoor units models: RPI-(4.0-6.0)FSRE
For the following indoor units: RCD, RPK, RCI, RCIM, RPF(I), RPI-(0.4-3.0)FNS5E, RPI-(8~20)FSN3(P)E, this function is
not used.
d5 – Prevention of decrease of heating discharge air temperature
This function prevents a drop in the air temperature by decreasing the fan speed, apart from the settings on the remote
control.
d6 – Room temperature control for energy saving
This function saves energy when the outdoor temperature is lower than the air conditioning load.
The indoor unit is set to cooling Thermo-OFF when: T
out
(outside ambient temperature - out of the building) < T
in
d7 – Only for Econofresh: OA Damper minimum opening
This function is setting the minimum opening angle of the damper for fresh-air intake.
E1 – KPI ventilation mode
This function is used to set the unit ventilation mode with energy / heat recovery
This function is useful to set the heat exchanger ventilation mode. The setting condition and ventilation mode are shown
below:
Setting condition
Setting
Contents
00
Effective ventilation mode selection (ventilation with total heat exchanger or ventilation bypass) to save energy by
detecting the difference in temperature between indoors and outdoors.
01
Heat is exchanged continuously when the heat exchanger is started.
02
Heat is not continuously exchanged when the heat exchanger is started.