![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 283](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379283.webp)
7 Servicing
KPI-(252-2002)(E/X)4E - Energy recovery and active energy recovery ventilation units
SMGB0137 rev.0 - 05/2021
273
7
7.9.7
Removal of the damper motor
1
Unscrew the 6 screw form the service cover (f).
2
Unplug the connector that is inside the protection cap.
3
Unscrew the 2 screws that are fixing the motor brackets
4
Separate the damper motor from the housing
5
Remove the damper motor