7 Servicing
RCD-(0.8-6.0)FSR - 2-way cassette
SMGB0137 rev.0 - 05/2021
205
7
4
Removing Turbo Fan and Fan Motor:
a.
Hold the turbo fan and remove the fixing nut then remove the turbo fan.
b. Remove the 2 screws from the plate holding the fan motor lead wire then remove the fan motor.
c.
Remove the fan motor lead wire from 2 code clamp for evaporator partition plate.
d. Remove the fixing nut and 3 vibration insulation rubber fixing the fan motor then remove the fan motor.
e.
For RCD-(4.0-6.0)FSR, remove the fan motor lead wire from 1 code clamp for fan partition plate placed on the
centre of the indoor unit.
Remove the fixing nut and 3 vibration rubber fixing the fan motor the remove the fan motor.
f. For reassembling, fix the bell-mouth to the drain pan with fixing screws temporarily then fix the fan motor lead wire
to 2 code clamp for the evaporator partition plate.
For RCD-(4.0-6.0)FSR, fix the fan motor lead wire to 1 code clamp for the fan partition plate placed on the centre
of the indoor unit.
g.
Center the turbo fan and bell-mouth to get enough clearance then fasten the fixing screws.
RCD-(0.8-3.0)FSR
RCD-(4.0-6.0)FSR
Fan motor
Fixing nut
Fixing nut
Bell-mouth
Vibration insulation rubber
Turbo fan
Fixing screw
Fan motor
Turbo fan
Fixing nut
Fixing nut
Vibration
insulation rubber
Bell-mouth
Fixing screw