![Hitachi RCI-1.0FSR Скачать руководство пользователя страница 173](http://html.mh-extra.com/html/hitachi/rci-1-0fsr/rci-1-0fsr_service-manual_2139379173.webp)
5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
163
5
•
Common items
-
In case of changing from Thermo-ON to Thermo-OFF at the beginning of the automatic mode, the fan speed
during Thermo-OFF is that of right after Thermo-OFF. Also, the switching of fan speed is not performed during
Thermo-OFF. (When switching from Thermo-ON to Thermo-OFF, the maintenance of fan speed for 3 minutes is
released, and the switching of fan speed depending on temperature differential is carried out)
-
The target of the automatic switching is the part of the control which operates at the normal setting fan speed.
-
When using a room thermostat and in test run, it is set to setting fan speed.
-
Even in case that the heating circulator is enabled (Function selection b2=01), it is set to the fan speed of the
automatic indoor fan speed mode.
?
N O T E
• The maximum fan speed in “Auto” mode is “High”, unless EF function is also activated.
• Econofresh present, E1=01 and Fan speed setting is “Auto” mode, fan speed is fixed to “High”
EF
– Automatic indoor fan speed mode (supporting High H)
This function allows to increase the maximum fan speed to “High H” in “Auto” mode.
•
Cooling
Indoor control temperature (Ti2) - Setting temperature 2 (Ts2)
≥
2ºC: Setting fan speed
Indoor control temperature (Ti2) - Setting temperature 2 (Ts2)
≥
1ºC: Medium
Indoor control temperature (Ti2) - Setting temperature 2 (Ts2) < 1ºC: Low
•
Heating
Setting temperature 2 (Ts2) - Indoor control temperature (Ti2)
≥
2ºC: Setting fan speed
Setting temperature 2 (Ts2) - Indoor control temperature (Ti2)
≥
1ºC: Medium
Setting temperature 2 (Ts2) - Indoor control temperature (Ti2) < 1ºC: Low
•
Relation with the automatic indoor fan speed mode (EE)
Setting of
function
selection EF
Setting of
function
selection EE
Remote control setting
Auto
High H
High
Medium
Low
00
00
High~Low
High2
High
High
Low
00
01
High~Low
High2~Low
High~Low
Medium~Low
Low
01
00
High2~Low
High2
High
High
Low
01
01
High2~Low
High2~Low
High~Low
Medium~Low
Low
F0
– Not available
F1
– Automatic OFF timer setting
This function is used to switch off the timer automatically when the unit is started using the remote control.
It is not possible to cancel or change the timer off setting during automatic timer off setting. However, it can be cancelled
when the unit is stopped. When the unit is restarted, the off timer setting period is established according to the optional
setting. Do not set the functions “0C”-”0F” when two remote control switches are used in the same remote control group.
?
N O T E
This function is not available for control using CSNET Manager 2 or 7-day timer.
F2
– Remote control main-sub setting
This function is useful when configuring two remote controls for the same installation: one in main mode and the other in
secondary mode.