2-20
888-2523-001
7/26/05
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Analogue
2.11 Initial Cooling System Turn ON
NOTE:
For further Cooling System start up information see the Transcool technical man-
ual and Appendix B Cooling System Help section.
Verify trip levels for the Pump Module
pumps and Heat Exchanger fans inside
the Cooling Control Panel. If necessary,
rotate the contactor trip threshold to match
the full load current (FLC) of the
corresponding pump or fan motor. See
Table 2-7 on page 2-21 for reference.
Verify contactor trip is set to Manual. If
necessary, rotate the trip control to Man
for manual reset in the event of a trip.
Pump
Fan
Trip
Trip
Early Model Shown