5-Stufentransformatoren 
5-Step transformers 
Transformateurs à 5 plots 

 

TRE 0,4-2 

TR 0,4-2 

 

TRE 0,6-2 

TR 0,8-2 

 

TRE 1,6-2  

TR 2,5-2 

 

TRE 3,3-2  

TR 6,6 

 

TRE 6,5-2  

 

 

TRE 10-2 

 
 
 
 
 

 

Montageanleitung 
Mounting instructions 
Instructions de montage 

w w w . m a i c o - v e n t i l a t o r e n . c o m  

 

 

Содержание TRE 0,4-2

Страница 1: ...n 5 Step transformers Transformateurs 5 plots TRE 0 4 2 TR 0 4 2 TRE 0 6 2 TR 0 8 2 TRE 1 6 2 TR 2 5 2 TRE 3 3 2 TR 6 6 TRE 6 5 2 TRE 10 2 Montageanleitung Mounting instructions Instructions de montag...

Страница 2: ...2...

Страница 3: ...abelverschraubungen Schaltschrankschl ssel Betriebsanleitung Bohrschablone 2 Verwendete Warnsymbole GEFAHR Lebensgefahr Eine Nichtbeachtung kann zum Tod oder zu schweren K rperverletzungen f hren VORS...

Страница 4: ...Die ersten Ziffern in der Produkt bezeichnung stehen f r die Maximal belastbarkeit des Ger tes in Ampere Zum Beispiel betr gt diese f r TRE 3 3 2 Transformatoren maximal 3 3 A TRE Transformatoren 5 St...

Страница 5: ...Fehlanwendungen Ger t auf keinen Fall einsetzen in der N he von brennbaren Materialien Fl ssigkeiten oder Gasen in explosionsf higer Atmosph re 6 Montagevorbereitung Hinweise Leitungseinf hrung Aufpu...

Страница 6: ...tungsl ngen und Absicherungen Montage GEFAHR Verletzungsgefahr durch unzureichende Befestigung des 5 Stufentransformators Ger t nur senkrecht an W nden oder Konsolen mit ausreichender Tragf higkeit an...

Страница 7: ...egeln Inbetriebnahme Vor Inbetriebnahme alle System komponenten gem deren Betriebsanleitungen installieren bereinstimmung mit den technischen Daten kontrollieren siehe Typenschild Netzsicherung einsch...

Страница 8: ...lassen Nur Sicherungen mit Bemessungsdaten gem nachfolgender Angaben einsetzen G Sicherungseins tze TRE 0 4 2 T 0 5A 250V TRE 0 6 2 T 0 8A 250V TRE 1 6 2 T 2 0A 250V TRE 3 3 2 T 4 0A 250V TRE 6 5 2 T...

Страница 9: ...metal enclosure 2 cable glands switching cabinet key operating instructions drilling template 2 Warning symbols used DANGER Danger to life Disregard may lead to death or serious physical injuries CAUT...

Страница 10: ...in the product designation represent the maximum load capacity of the device in Ampere For example for TRE 3 3 2 transformers it is max 3 3 A TRE Transformers 5 step transformer for the speed adjustme...

Страница 11: ...rcumstance in the vicinity of combustible materials liquids or gases in explosive atmosphere 6 Mounting preparation Notes Surface cable introduction The enclosure must not be exposed to any mechanical...

Страница 12: ...ross section cable lengths and fuses Mounting DANGER Risk of injury through inadequate fastening of the 5 step transformer Mount device only vertically on walls or consoles with sufficient weight bear...

Страница 13: ...Close switching cabinet door and lock with cabinet key Startup Before startup install all system components according to their operating instructions Verify agreement with the technical data see type...

Страница 14: ...sary Use only fuses with ratings according to the following specifications G fuse inserts TRE 0 4 2 T 0 5A 250V TRE 0 6 2 T 0 8A 250V TRE 1 6 2 T 2 0A 250V TRE 3 3 2 T 4 0A 250V TRE 6 5 2 T 8 0A 250V...

Страница 15: ...2 vissages de c bles cl d armoire lectrique notice d utilisation gabarit de per age 2 Symboles d avertissement utilis s DANGER Danger de mort Le non respect peut entrainer la mort ou de graves blessur...

Страница 16: ...tilateur 6 5 Porte du logement 6 6 Cl du logement T tiquette signal tique Description du produit Les premiers chiffres de la d signation du produit correspondent la charge maximale de l appareil en Am...

Страница 17: ...enduit dans les espaces int rieurs Mauvaises utilisations pr visibles Ne jamais utiliser l appareil proximit de mat riaux liquides ou gaz inflammables dans des atmosph res risque d explosion 6 Pr par...

Страница 18: ...s et protections Montage DANGER Risque de blessure par un fixation insuffisante du transformateur 5 niveaux Apposer l appareil exclusivement la verticale des murs ou consoles ayant une portance suffis...

Страница 19: ...cl d armoire lectrique Mise en service Installer avant la mise en service tous les composants du syst me suivant la notice d utilisation V rifier la coh rence avec les caract ristiques techniques voir...

Страница 20: ...ser exclusivement des fusibles aux bonnes dimensions suivant les indications ci apr s Utilisation de fusibles G TRE 0 4 2 T 0 5A 250V TRE 0 6 2 T 0 8A 250V TRE 1 6 2 T 2 0A 250V TRE 3 3 2 T 4 0A 250V...

Страница 21: ...21 D GB F 11 Schaltbilder Wiring diagrams Sch mas de branchement...

Страница 22: ...22 D GB F Schaltbilder Wiring diagrams Sch mas de branchement...

Страница 23: ...23...