Preparations on enclosure type 

TRE 0,4-2, TRE 0,6-2 and TRE 1,6-2 
TRE 3,3-2, TRE 6,5-2 and TRE 10-2 
TR 0,4-2 TR 0,8-2 and TR 2,5-2   
 

Set enclosure cover aside. 

 Pull off the plug of the connecting cable at 

the ready light (see Fig. page 6). 

 With all types, insert the cable glands into 

the holes provided in the enclosure bottom 
and screw tight with lock nut. 

 Cap nut torque 2.5 Nm 

 Lock nut torque 2.5 Nm 

 
 

Preparations on enclosure type 

TR 6,6-2

 

 Open enclosure door [2.5] with enclosure 

key [2.6]. 

 Insert the cable glands into the holes 

provided in the enclosure bottom and 
screw tight with lock nut. 

 Cap nut torque 2.5 Nm  

 Lock nut torque 2.5 Nm  

 
 

Note: 

This connection information does not replace 
the operating instructions of the installation by 
the plant manufacturer. When making the 
electrical connection of the device, the 
directions in the operating instructions of the 
installation must be followed (amongst others, 
line cross-section, cable lengths and fuses)!

 

Mounting

 

 

DANGER 

Risk of injury through 
inadequate fastening of the 5-
step transformer! 

 Mount device only vertically on 

walls or consoles with 
sufficient weight-bearing 
capacity. 

 Provide fasteners with 

adequate dimensions at the 
installation site! 

 

CAUTION 

Protection class not ensured if 
incorrectly mounted! 

 Always screw down the device 

with the 4 mounting screws 
inserted through the provided 
enclosure holes. 

 Place the enclosed caps on 

the screw heads. 

 
 

Mounting the enclosure bottom 

 Screw enclosure bottom firmly against the 

wall/console at the installation location. 

 
 

Electrical connection 

 

DANGER 

Danger to life! 

 Disconnect mains fuse! 

 Post warning sign against 

inadvertent reactivation well 
visibly. 

 

CAUTION 

Risk of short circuit through 
moisture if cables are 
introduced incorrectly into the 
transformer enclosure! 

 Guide cable properly through 

cable bushings or cable 
glands. Tighten the glands 
when using cable glands. 

 See torque in Section 6 

 Make the electrical connection at the 

terminal, see circuit diagram in the 
transformer or pages 6 and 7 of these 
mounting instructions. 

 
 

Содержание TRE 0,4-2

Страница 1: ...n 5 Step transformers Transformateurs 5 plots TRE 0 4 2 TR 0 4 2 TRE 0 6 2 TR 0 8 2 TRE 1 6 2 TR 2 5 2 TRE 3 3 2 TR 6 6 TRE 6 5 2 TRE 10 2 Montageanleitung Mounting instructions Instructions de montag...

Страница 2: ...2...

Страница 3: ...abelverschraubungen Schaltschrankschl ssel Betriebsanleitung Bohrschablone 2 Verwendete Warnsymbole GEFAHR Lebensgefahr Eine Nichtbeachtung kann zum Tod oder zu schweren K rperverletzungen f hren VORS...

Страница 4: ...Die ersten Ziffern in der Produkt bezeichnung stehen f r die Maximal belastbarkeit des Ger tes in Ampere Zum Beispiel betr gt diese f r TRE 3 3 2 Transformatoren maximal 3 3 A TRE Transformatoren 5 St...

Страница 5: ...Fehlanwendungen Ger t auf keinen Fall einsetzen in der N he von brennbaren Materialien Fl ssigkeiten oder Gasen in explosionsf higer Atmosph re 6 Montagevorbereitung Hinweise Leitungseinf hrung Aufpu...

Страница 6: ...tungsl ngen und Absicherungen Montage GEFAHR Verletzungsgefahr durch unzureichende Befestigung des 5 Stufentransformators Ger t nur senkrecht an W nden oder Konsolen mit ausreichender Tragf higkeit an...

Страница 7: ...egeln Inbetriebnahme Vor Inbetriebnahme alle System komponenten gem deren Betriebsanleitungen installieren bereinstimmung mit den technischen Daten kontrollieren siehe Typenschild Netzsicherung einsch...

Страница 8: ...lassen Nur Sicherungen mit Bemessungsdaten gem nachfolgender Angaben einsetzen G Sicherungseins tze TRE 0 4 2 T 0 5A 250V TRE 0 6 2 T 0 8A 250V TRE 1 6 2 T 2 0A 250V TRE 3 3 2 T 4 0A 250V TRE 6 5 2 T...

Страница 9: ...metal enclosure 2 cable glands switching cabinet key operating instructions drilling template 2 Warning symbols used DANGER Danger to life Disregard may lead to death or serious physical injuries CAUT...

Страница 10: ...in the product designation represent the maximum load capacity of the device in Ampere For example for TRE 3 3 2 transformers it is max 3 3 A TRE Transformers 5 step transformer for the speed adjustme...

Страница 11: ...rcumstance in the vicinity of combustible materials liquids or gases in explosive atmosphere 6 Mounting preparation Notes Surface cable introduction The enclosure must not be exposed to any mechanical...

Страница 12: ...ross section cable lengths and fuses Mounting DANGER Risk of injury through inadequate fastening of the 5 step transformer Mount device only vertically on walls or consoles with sufficient weight bear...

Страница 13: ...Close switching cabinet door and lock with cabinet key Startup Before startup install all system components according to their operating instructions Verify agreement with the technical data see type...

Страница 14: ...sary Use only fuses with ratings according to the following specifications G fuse inserts TRE 0 4 2 T 0 5A 250V TRE 0 6 2 T 0 8A 250V TRE 1 6 2 T 2 0A 250V TRE 3 3 2 T 4 0A 250V TRE 6 5 2 T 8 0A 250V...

Страница 15: ...2 vissages de c bles cl d armoire lectrique notice d utilisation gabarit de per age 2 Symboles d avertissement utilis s DANGER Danger de mort Le non respect peut entrainer la mort ou de graves blessur...

Страница 16: ...tilateur 6 5 Porte du logement 6 6 Cl du logement T tiquette signal tique Description du produit Les premiers chiffres de la d signation du produit correspondent la charge maximale de l appareil en Am...

Страница 17: ...enduit dans les espaces int rieurs Mauvaises utilisations pr visibles Ne jamais utiliser l appareil proximit de mat riaux liquides ou gaz inflammables dans des atmosph res risque d explosion 6 Pr par...

Страница 18: ...s et protections Montage DANGER Risque de blessure par un fixation insuffisante du transformateur 5 niveaux Apposer l appareil exclusivement la verticale des murs ou consoles ayant une portance suffis...

Страница 19: ...cl d armoire lectrique Mise en service Installer avant la mise en service tous les composants du syst me suivant la notice d utilisation V rifier la coh rence avec les caract ristiques techniques voir...

Страница 20: ...ser exclusivement des fusibles aux bonnes dimensions suivant les indications ci apr s Utilisation de fusibles G TRE 0 4 2 T 0 5A 250V TRE 0 6 2 T 0 8A 250V TRE 1 6 2 T 2 0A 250V TRE 3 3 2 T 4 0A 250V...

Страница 21: ...21 D GB F 11 Schaltbilder Wiring diagrams Sch mas de branchement...

Страница 22: ...22 D GB F Schaltbilder Wiring diagrams Sch mas de branchement...

Страница 23: ...23...

Страница 24: ...24 Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Germany Service 49 7720 694 447 technik maico de 06 14_Wi...

Отзывы: