Operation and installation manual

 

CO K5X 002 – KNX RF/TP Coupler

 

 
 

 

 
Application 

The KNX RF/TP Coupler is a compact KNX radio coupler. It 
connects KNX RF devices of a radio line with the KNX Bus 
Twisted Pair. 

The device has a filter table for group addresses. The coupler 
supports long frames and is compatible with the ETS® software 
ETS5 or higher. 

The buttons on the front panel allow disabling the telegram filter 
for testing purposes. The LEDs indicate operating conditions as 
well as communication errors on the KNX bus. 

The power is supplied via the KNX bus. 

Coupler function 

 

KNX RF/TP Coupler as line coupler 

 
The individual address assigned to the KNX RF/TP Coupler in 
the form of x.y.0 (x, y: 1..15) sets up, that the device operates as 
a line coupler.  

The KNX RF/TP Coupler has a filter table and thus contributes to 
reducing the bus load. The filter table supports the extended 
group address range (main group 0..31) and is automatically 
generated by the ETS. 

Installation and Connection 

The device can be flush-mounted, the housing fits into a stan-
dard flush-mounted box. 

When choosing the installation location the range of RF devices 
to be associated with the gateway has to be considered. Shield-
ing objects (e.g. metal cabinets) or interfering transmitters (e.g. 
computers, electronic transformers, ballasts) near the gateway 
should be avoided. 

The connection to the KNX bus is made with a bus connector. 
The correct polarity of the terminal referred to the printing inside 
the unit has to be considered. 

The KNX RF/TP Coupler features the following controls and 
displays: 

 

 

An external power supply is not necessary as the device is 
powered by the KNX bus. 

 
The device is not working without bus power.

 

 

KNX Programming mode 

The KNX programming mode is activated/deactivated by press-

ing the KNX programming button 

. When the programming 

mode is active, the programming LED 

 

lights red.  

A gateway ex-factory has the default individual address 15.15.0. 

 

 

Manual operation and status display 

The State LED 

 lights up if the device is successfully powered 

by the KNX bus. This LED blinks red, when the application is not 

running, e.g. after a failed ETS download. The State LED 

 

lights up orange to indicate that manual operation is active.  

The LEDs 1-4 

❺ 

show TP traffic. 

The LEDs 5-8 

❺ 

show RF traffic. 

Manual operation TP 

Pressing button A 

 short, enters the manual operation for TP 

mode. 

By pressing button A 

, routing runtime telegrams (group 

telegrams) will be enabled/disabled. This will be indicated by 
LEDs 1 and 2 

.  

By pressing button B 

, routing management telegrams (indi-

vidual addressed and broadcast telegrams) will be 
enabled/disabled. This will be indicated by LEDs 3 and 4 

EN 

 Button P KNX Prog 

 

LED P KNX Prog 

 

KNX bus connector 

 LED S State 

 LEDs 1-8  

 Button A 

❼ 

Button B 

 

 

 

Reviews: