2-10
888-2523-001
7/26/05
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Analogue
NOTE:
Condensation can occur in the conduit leading to the outside heat exchanger from
the control panel. This conduit should be caulked or sealed after the system is
tested and operational.
Table 2-4 Heat Exchanger Control and Status Connections
Cooling Control Panel
Heat Exchanger
X2-25
X1-9
X2-26
X1-10
X2-27
X1-11
X2-28
X1-12
X2-29
X1-20 (3rd Fan Only)
X2-30
X1-21 (3rd Fan Only)
X2-18 (2 conductors)
X1-13 (2 conductors)
X2-19 (2 conductors)
X1-14 (2 conductors)
X2-20 (2 conductors)
X1-15 (2 conductors)
X2-17
X1-16(GND)
These connections should be verified using Schematic
The Gray rows require
2 conductors be used
on each terminal for
current capacity.
NOTE: