WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Analogue
J15-2
+5VDC_ISOLATED
Output: Install jumper to J15-11
to use internal supply for status
pull ups. Otherwise an external
supply will have to be connected
to J15-11.
J15-3
/OUTPUT 9
VSWR Foldback ON
L= Foldback ON
H= Foldback OFF
J15-4
/OUTPUT 10
Transmitter Faulted OFF
L= Fault OFF
H= TX OK
J15-5
/OUTPUT 11
Drive Chain Fault
L= FAULT
H= OK
J15-6
/OUTPUT 12
Cooling Fault
L= FAULT
H= OK
J15-7
/OUTPUT 13
Summary Fault
L= FAULT
H= OK
J15-8
/OUTPUT 14
Transmitter OFF and not Faulted
L= TX OFF not faulted
H=TX ON
J15-9
/OUTPUT 15
RF Switch A/B Status
L= POSITION A
H= POSITION B
J15-10
/OUTPUT 16
RF Switch
Drive A/B to motorized switch
L= POSITION A
H= POSITION B
J15-11
+VDC EXT SUPPLY
Input For External Pull Up
Supply Voltage
J15-12
GNDB
Isolated Ground
Table 2-12 J15 & J16, External I/O Board, Remote Status Outputs
Connector
and pin #
Schematic Label
Status Output
Status Type and Polarity
Содержание ATLAS ANALOGUE
Страница 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 14: ...Table of Contents continued 4...
Страница 114: ...3 40 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing Section 3 Operation ATLAS Analogue...