2-34
888-2523-001
7/26/05
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Analogue
Verify the control settings and adjust if necessary. Inside the Heat Exchanger panel,
verify that the control setting for the left (Fan A) and right (Fan B) thermostats are set at
32
o
C and 38ºC, respectively, which will switch fan A on when the coolant temperature
reaches 32
o
C, and Fan B on if the temperature raises to 38
o
C.
The +/- adjustment controls the differential when the fans will switch off, which is
factory set to 4
o
C for both. This will switch Fan A off when the temperature cools to
28
o
C, and Fan B will turn off when the coolant temperature reaches 34
o
C.
2.13.1.4 Verifying Pump Switching
In modules with dual pumps, verify that both pumps operate properly by
switching pumps back and forth from the GUI screen. Also verify that correct flow
rate is achieved with either pump active.
•
Press SYSTEM then SYSTEM COOLING. This screen is shown in Figure 3-
25 on page 3-27.
•
Select manual pump switching. Button should display MANUAL
ENABLED.
•
Press pump select button for PUMP A ON then PUMP B ON. The pumps
should switch. This is indicated in the transmitter GUI screen, as well as in
the Cooling Control Panel status LED indicators.
2.13.1.5 Normal Pump Operation
In normal operation (Cooling Control Panel set for Remote), the transmitter commands
the pump selection. If there is a need for operating the pump module independently
from the transmitter, the Local button on the Cooling Control Panel should be activated.
Check coolant level status. Verify the coolant level indicator LEDs are not be lit. If
they are, there is insufficient coolant in the system. Add coolant to the tank until no
alarms are shown on the cooling control panel or GUI.
Press the Remote button on the Cooling Control Panel (green LED should
illuminate). With testing completed, this will be the normal operating mode.
2.13.2 Setting Exciter Parameters
See TVS-D660 Exciter manuals to set exciter parameters.
Содержание ATLAS ANALOGUE
Страница 4: ...iv 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 6: ...vi 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 8: ...viii 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 10: ...x 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing...
Страница 14: ...Table of Contents continued 4...
Страница 114: ...3 40 888 2523 001 7 26 05 WARNING Disconnect primary power prior to servicing Section 3 Operation ATLAS Analogue...